Micropilot M FMR244
产品描述
连续的非接触式物位测量仪表。
经济的4 - 20 mA 两线制技术,适用于危险区域。
连续的非接触式物位测量仪表。
经济的4 - 20 mA 两线制技术,适用于危险区域。
优点
- 经济的两线制技术:
是差压、浮子和浮筒式物位计的可靠替代品。
采用两线制技术,有效的降低布线成本,且易于实现与现有系统的集成 - 非接触式测量
测量几乎不受介质特性影响 - 通过数文引导式菜单轻松进行现场操作.
- 通过Endress+Hauser的操作软件便于进行仪表调试、文件编制和故障诊断
- 频率范围采用K波段
- 支持HART 或PROFIBUS PA以及FF基金会现场总线协议
- 用于物位监测(MIN, MAX) ,符合 IEC 61508/IEC 61511-1标准的要求,通过了SIL 2 认证
应用领域
Micropilot M可用于对液体、浆料、淤泥和固料进行连续的非接触式物位测量。测量不受介质改变,温度变化,气压或蒸汽的影响。
FMR244不仅具有喇叭天线的优势,而且还具有极强的抗化学腐蚀性。80mm(3")喇叭天线还可以用于固体测量.
技术参数
Continuous / Liquids
Continuous / Solids
测量原理 | Level radar | |
Characteristic / Application | Small horn with high chemical compatibility | |
Supply / Communication | 2-wire (HART / PROFIBUS PA / FOUNDATION Fieldbus) | |
Frequency | K-band (~26 GHz) | |
Accuracy | +/- 3 mm | |
Ambient temperature | -40 °C...+80 °C (-40 °F...+176 °F) | |
Process temperature | -40 °C...+130 °C (-40 °F...+266 °F) | |
Process pressure absolute / max. overpressure limit | Vacuum...3 bar (Vacuum...43.5 psi) | |
Main wetted parts | PVDF, PTFE, PP, PBT | |
Process connection | Thread: NPT 1 1/2, G 1 1/2 Slip on flange: DN80...DN150 (3"...6"), | |
Max. measurement distance | Standard: 20m (65ft) With additional option F (G): 25m (82ft) | |
![]() |
![]() | |
Output | 4...20 mA HART PROFIBUS PA FOUNDATION Fieldbus | |
Certificates / Approvals | ATEX, FM, CSA, IECEx, TIIS, NEPSI Overfill prevention WHG SIL Marine GL/ABS/NK | |
Application limits | Maximum measuring range is dependent on the tank form and/or application Ammoniacal gas phase FMR230 in stilling well Strong buildup formation FMR230 with air purge Low DK FMR240 Only PTFE resistant FMR245 Custody transfer measurement FMR540 |
测量原理 | Level radar | |
Characteristic / Application | Non-contact level measurement in powdery to granular bulk solids up to 15m measurering range. Applications with highly abrasive bulk solids e.g. ferrite / glas ... | |
Supply / Communication | 2-wire (HART / PROFIBUS PA / FOUNDATION Fieldbus) | |
Frequency | K-band (~26 GHz ) | |
Antenna | Horn DN80/3" | |
Accuracy | +/- 15 mm (or 0.04% of range, whatever is larger) | |
Ambient temperature | -40 °C...+80 °C (-40 °F...+266 °F) | |
Process temperature | -40 °C...+80 °C (-40 °F...+266 °F) | |
Process pressure absolute / max. overpressure limit | Vacuum... 3bar (Vaccum... 43.5 psi) | |
Main wetted parts | PP, PBT, Silicone | |
Process connection | Flange: UNI DN80...DN150 | |
Max. measurement distance | 15m (49 ft)(Option F) | |
Output | 4...20 mA HART PROFIBUS PA FOUNDATION Fieldbus | |
Certificates / Approvals | ATEX, FM, CSA, IECEx, TIIS, NEPSI | |
Options | Separate display Mounting bracket variable flange seal for adjustment | |
Application limits | Dk < 1.6 | |
Successor | Micropilot FMR56 |